Sale! View larger

AWWA ACE71106

New product

AWWA ACE71106 Maximizing Fire and Emergency Storage without Compromising Water Quality

Conference Proceeding by American Water Works Association, 11/01/2009

Oppenhiemer, Jason

More details

$12.00

-50%

$24.00

More info

Full Description

This poster paper presents a situation at Spanaway, Washington, where operators of a 1.5 mg steel standpipe suspected thermal stratification upon noticing condensation on the outside of the tank abruptly stopped about 20 feet up the side of the tank. A pronounced thermal stratification of more than 10 degrees C was discovered, with a distinct thermocline between 20 ft. and 40 ft. from the bottom of the tank. A submersible active mixer was installed to restore water quality and residual throughout the standpipe. The poster paper describes how the mixing system works.

Product Details

Edition: Vol. - No. Published: 11/01/2009 Number of Pages: 1File Size: 1 file , 2.3 MB