AWWA ACE70859 The Effect of Partial Lead Service Line Replacements on Lead Leaching

Conference Proceeding by American Water Works Association, 11/01/2009

Nguyen, Caroline; Triantafyllidou, Simoni; Hu, Jie; Edwards, Marc

More details

$12.00

-50%

$24.00

More info

Full Description

This powerpoint presentation begins by providing a brief overview of the adverse consequences of partial pipe replacements and the practical concernsrelated to galvanic corrosion andPSR. Topics presented include: chloride to sulfatemass ratio (CSMR)sample calculation; causes for concern - high CSMR; and, experimental design -Cu2+ Deposition Corrosion. Cu2+ Deposition Corrosionconclusions:trace levels of Cu2+ (even 0.03 mg/L)increased lead release from lead pipe w/nogalvanic connection to Cu;deposition corrosion significant concern interms of lead leaching as per prior research; and,putting a copper pipe before a lead pipe inthe flow path, as occurs in partialreplacement, is a concern. Mechanisms ofgalvanic corrosion(Pb Pipe - Cu Pipe),new vs. aged Pb pipeCSMR is presented, along with simulated small scalepartial replacements. Conclusions indicate that:Cu2+ in water increases Pb in water(deposition corrosion); galvanic corrosion of Pb/Cu couples can besignificant - lower pH and higher Cl- at Pb junctionduring stagnation, andPb is sacrificed; simulated partial service line replacement,higher Pb ( 200%) in low CSMR water,higher Pb (165%) in high CSMR water, andshort length of Cu relative to Pb hadhighest Pb release. Includes tables, figures.

Product Details

Edition: Vol. - No. Published: 11/01/2009 Number of Pages: 54File Size: 1 file , 2 MB